Fuel Feed
Units: °F °C
Index Name Units Boiler 1Boiler 2
Current Value Last Changed Prev. ValueCurrent ValueLast ChangedPrev. Value
33 Minimum loading rate % 4 2014-12-18 13:52:37 (GMT-5) 14 4 2014-12-18 13:52:40 (GMT-5) 14
46 Delivery time feed screw s 10.0 2013-10-26 01:26:04 (GMT-5) 10.0 10.0 2013-10-26 01:26:12 (GMT-5) 10.0
872 Stoker monitoring active 1 2013-10-26 01:26:04 (GMT-5) 1 1 2013-10-26 01:26:12 (GMT-5) 1
52 Minimum duration of blower fan run-on 1 (for res. O2) m 15 2013-10-26 01:26:04 (GMT-5) 15 15 2013-10-26 01:26:12 (GMT-5) 15
53 Minimum duration of blower fan run-on 2 (for flue gas) m 5 2013-11-21 10:00:13 (GMT-5) 2 5 2014-01-31 18:17:55 (GMT-5) 2
516 Pause before cleaning/During heating-cleaning reduce output for m 30 2013-10-26 01:26:04 (GMT-5) 30 30 2013-10-26 01:26:12 (GMT-5) 30
60 WOS runtime s 60 2013-10-26 01:26:04 (GMT-5) 60 60 2013-10-26 01:26:12 (GMT-5) 60
476 Cycle of ash screw s 800 2013-11-22 10:34:50 (GMT-5) 1000 1000 2014-01-16 14:41:27 (GMT-5) 800
477 Runtime of the ash screw s 80 2013-11-22 10:01:33 (GMT-5) 70 80 2013-11-22 10:27:28 (GMT-5) 70
825 Heating hours until ash removal warning h 9000 2013-10-26 01:26:04 (GMT-5) 9000 9000 2013-10-26 01:26:12 (GMT-5) 9000
921 Clean after how many hours heating h 8.0 2015-05-21 14:50:04 (GMT-5) 12.0 8.0 2015-10-14 14:37:35 (GMT-5) 6.0
511 Clean after how many shutdowns/T4: Tilt Grate How Often During Cleaning 0 2014-11-21 16:33:53 (GMT-5) 1 0 2014-11-21 16:42:04 (GMT-5) 1