Parameters Parameters
Units: °F °C  |  Display Items Changed in: Full History Last Week Last 24 Hours Last Hour Specify Period  |  Cells highlighted in green indicate different current parameter settings.
Index Parameter Name Units Boiler 1Boiler 2
Current Value Last Changed Prev. Value ChangedCurrent ValueLast ChangedPrev. ValueChanged
1 Shutdown if current boiler temperature is higher than boiler setpoint + Δ°C 9.0 2014-03-06 10:32:05 (GMT-5) 5.0 2013-12-27 10:28:14 (GMT-5) 9.0 2014-03-06 10:37:25 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
2 Maximum heating up time during which HEATING status must be reached m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
3 Minimum flue gas temperature °C 120.0 2013-12-27 10:28:14 (GMT-5) 120.0 2013-12-27 10:28:22 (GMT-5)
4 Maximum flue gas temperature °C 250.0 2013-12-27 10:28:14 (GMT-5) 250.0 2013-12-27 10:28:22 (GMT-5)
5 Minimum difference between flue gas temperature and boiler temperature Δ°C 7.0 2013-12-27 10:28:14 (GMT-5) 10.0 2014-01-10 08:51:27 (GMT-5) 15.0 2014-01-10 08:48:11 (GMT-5)
6 Minimum boiler temperature to release all pumps °C 65.0 2013-12-27 10:28:14 (GMT-5) 65.0 2013-12-27 10:28:22 (GMT-5)
7 8 2013-12-27 10:28:14 (GMT-5) 8 2013-12-27 10:28:22 (GMT-5)
8 Maximum boiler setpoint °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 2013-12-27 10:28:22 (GMT-5)
9 Always switch off at maximum boiler setpoint + Δ°C 3.0 2014-03-06 10:32:05 (GMT-5) 5.0 2013-12-27 10:28:14 (GMT-5) 3.0 2014-03-06 10:37:25 (GMT-5) 5.0 2014-01-24 10:07:16 (GMT-5)
10 Primary air opening at 0% signal % 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
11 Primary air opening at 100% signal % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
12 Secondary air opening at 0% signal % 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
13 Secondary air opening at 100% signal % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
14 Safety time for checking for air leaks min 90 2013-12-27 10:28:14 (GMT-5) 90 2013-12-27 10:28:22 (GMT-5)
15 Primary air during slumber % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
16 Controller gain for water controller Kp 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
17 Reset time for water controller Tn s 450 2013-12-27 10:28:14 (GMT-5) 450 2013-12-27 10:28:22 (GMT-5)
18 Controller gain for flue gas controller Kp 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
19 Reset time for flue gas controller Tn s 350 2013-12-27 10:28:14 (GMT-5) 350 2013-12-27 10:28:22 (GMT-5)
20 Gain for O2 controller Kp (TX)/T4: Slide-in gain 0.35 2013-12-27 10:28:14 (GMT-5) 0.35 2013-12-27 10:28:22 (GMT-5)
21 Reset time for O2 regulator Tn (TX)/T4: Slide-in reset time s 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
22 Start increase of flue gas temperature Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
23 ID fan min % 20 2013-12-27 10:28:14 (GMT-5) 16 2014-01-10 08:48:11 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
24 ID fan max % 75 2013-12-27 10:28:14 (GMT-5) 80 2014-01-10 08:48:11 (GMT-5) 76 2013-12-27 10:28:22 (GMT-5)
25 Minimum primary air % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
26 Primary air 100 % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
27 Secondary air maximum without lambda probe % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
28 Secondary air delay s 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
29 Boiler temperature setpoint °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 2013-12-27 10:28:22 (GMT-5)
30 residual oxygen content setpoint % 8.0 2013-12-27 10:28:14 (GMT-5) 8.0 2013-12-27 10:28:22 (GMT-5)
31 Residual oxygen content above which it switches to SHUTDOWN % 19.5 2013-12-27 10:28:14 (GMT-5) 19.5 2013-12-27 10:28:22 (GMT-5)
32 Maximum loading rate % 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
33 Minimum loading rate % 5 2013-12-27 10:28:14 (GMT-5) 5 2014-01-10 08:48:11 (GMT-5) 4 2013-12-27 10:28:22 (GMT-5)
34 O2 Controller max/T4: Slide-in control % 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
35 Influencing factor for O2 controller 1.50 2013-12-27 10:28:14 (GMT-5) 1.50 2013-12-27 10:28:22 (GMT-5)
36 Controller gain for O2 controller Kp 0.15 2013-12-27 10:28:14 (GMT-5) 0.15 2013-12-27 10:28:22 (GMT-5)
37 Reset time for O2 regulator Tn s 95 2013-12-27 10:28:14 (GMT-5) 95 2013-12-27 10:28:22 (GMT-5)
38 O2 controller Td 0.10 2013-12-27 10:28:14 (GMT-5) 0.10 2013-12-27 10:28:22 (GMT-5)
39 O2 controller sampling rate 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
40 No feed when residual O2 below % 4.5 2013-12-27 10:28:14 (GMT-5) 4.5 2013-12-27 10:28:22 (GMT-5)
41 Boiler output at flue gas temperature of 20°C % 60 2013-12-27 10:28:14 (GMT-5) 50 2014-01-10 08:48:11 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
42 100% boiler output from a flue gas temperature of °C 90.0 2013-12-27 10:28:14 (GMT-5) 90.0 2014-01-10 08:48:11 (GMT-5) 85.0 2013-12-27 10:28:22 (GMT-5)
43 Pellet fan min % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
44 Pellet fan max % 80 2013-12-27 10:28:14 (GMT-5) 80 2013-12-27 10:28:22 (GMT-5)
45 Minimum ID fan speed % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
46 Delivery time feed screw s 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
47 Mode (transition/winter...) 2 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
48 Feed time before ignition s 85 2013-12-27 10:28:14 (GMT-5) 75 2014-01-10 08:48:11 (GMT-5) 80 2013-12-27 10:28:22 (GMT-5)
49 Duration of pre-heating s 450 2013-12-27 10:28:14 (GMT-5) 400 2014-01-10 08:48:11 (GMT-5) 450 2013-12-27 10:28:22 (GMT-5)
50 Flue gas - flue gas difference preheat->htg mode Δ°C 12.0 2013-12-27 10:28:14 (GMT-5) 15.0 2014-01-10 08:51:27 (GMT-5) 10.0 2014-01-10 08:48:11 (GMT-5)
51 Maximum ignition duration m 15 2013-12-27 10:28:14 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
52 Minimum duration of blower fan run-on 1 (for res. O2) m 15 2020-10-15 12:54:47 (GMT-5) 0 2020-10-15 12:51:36 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
53 Minimum duration of blower fan run-on 2 (for flue gas) m 5 2020-10-15 12:54:47 (GMT-5) 0 2020-10-15 12:51:36 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
54 Safety time m 8 2013-12-27 10:28:14 (GMT-5) 8 2014-01-10 08:48:11 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
55 ID fan during heating up % 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
56 ID Fan during pre-heating % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
57 Slide-in during ignition % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
58 ID fan during shutdown % 70 2013-12-27 10:28:14 (GMT-5) 65 2013-12-27 10:28:22 (GMT-5)
59 ID fan during Ignition % 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
60 WOS runtime s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
61 Start of 1st pellet filling h 4.50 2013-12-27 10:28:14 (GMT-5) 2.50 2014-01-24 09:52:28 (GMT-5) 3.50 2014-01-10 08:49:11 (GMT-5)
62 Preliminary suction time s 5 2013-12-27 10:28:14 (GMT-5) 0 2014-01-10 08:48:11 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
63 Screw cycle s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
64 Suction run-on s 15 2013-12-27 10:28:14 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
65 Refill of cyclone from % 0 2014-08-11 16:02:40 (GMT-5) 45 2013-12-27 10:28:14 (GMT-5) 0 2014-08-11 15:58:28 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
66 Number of screw cycles 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
67 Minimum return temperature °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
68 Controller gain for shunt pump Kp-Kr 0.70 2013-12-27 10:28:14 (GMT-5) 0.70 2013-12-27 10:28:22 (GMT-5)
69 Controller reset time s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
70 Minimum speed of shunt pump % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
71 Slide-in during heating-cleaning % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
72 Proportional factor for mixer control RL 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
73 Controller reset time RL s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
74 Mixer runtime RL s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
75 Heating circuit overheat in variable mode Δ°C 2.0 2013-12-27 10:28:14 (GMT-5) 2.0 2014-01-10 08:48:11 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
76 Variable mode activated 0 2013-12-27 10:28:14 (GMT-5) 0 2014-01-10 08:48:11 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
77 Desired room temperature during heating mode HK 1 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
78 Desired room temperature during setback mode HK 1 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
79 Controller gain room temperature Kp-Rm HK 1 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
80 Reduction of flow temperature in setback mode HK 1 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
81 External temperature HK 1 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
82 External temperature HK 1 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
83 Maximum flow temperature HK 1 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
84 Proportional factor for mixer control HK 1 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
85 Controller reset time HK 1 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
86 Mixer runtime HK 1 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
87 Frost protection temperature HK 1 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
88 Flow temperature SP at external temperature of -10°C HK 1 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
89 Flow temperature SP at external temperature of +10°C HK 1 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
90 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
91 Desired room temperature during heating mode HK 2 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
92 Desired room temperature during setback mode HK 2 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
93 Controller gain room temperature Kp-Rm HK 2 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
94 Reduction of flow temperature in setback mode HK 2 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
95 External temperature HK 2 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
96 External temperature HK 2 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
97 Maximum flow temperature HK 2 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
98 Proportional factor for mixer control HK 2 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
99 Controller reset time HK 2 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
100 Mixer runtime HK 2 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
101 Frost protection temperature HK 2 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
102 Flow temperature SP at external temperature of -10°C HK 2 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
103 Flow temperature SP at external temperature of +10°C HK 2 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
104 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
105 Desired room temperature during heating mode HK 3 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
106 Desired room temperature during setback mode HK 3 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
107 Controller gain room temperature Kp-Rm HK 3 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
108 Reduction of flow temperature in setback mode HK 3 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
109 External temperature HK 3 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
110 External temperature HK 3 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
111 Maximum flow temperature HK 3 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
112 Proportional factor for mixer control HK 3 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
113 Controller reset time HK 3 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
114 Mixer runtime HK 3 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
115 Frost protection temperature HK 3 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
116 Flow temperature SP at external temperature of -10°C HK 3 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
117 Flow temperature SP at external temperature of +10°C HK 3 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
118 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
119 Desired room temperature during heating mode HK 4 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
120 Desired room temperature during setback mode HK 4 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
121 Controller gain room temperature Kp-Rm HK 4 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
122 Reduction of flow temperature in setback mode HK 4 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
123 External temperature HK 4 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
124 External temperature HK 4 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
125 Maximum flow temperature HK 4 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
126 Proportional factor for mixer control HK 4 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
127 Controller reset time HK 4 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
128 Mixer runtime HK 4 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
129 Frost protection temperature HK 4 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
130 Flow temperature SP at external temperature of -10°C HK 4 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
131 Flow temperature SP at external temperature of +10°C HK 4 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
132 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
133 Desired room temperature during heating mode HK 5 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
134 Desired room temperature during setback mode HK 5 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
135 Controller gain room temperature Kp-Rm HK 5 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
136 Reduction of flow temperature in setback mode HK 5 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
137 External temperature HK 5 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
138 External temperature HK 5 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
139 Maximum flow temperature HK 5 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
140 Proportional factor for mixer control HK 5 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
141 Controller reset time HK 5 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
142 Mixer runtime HK 5 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
143 Frost protection temperature HK 5 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
144 Flow temperature SP at external temperature of -10°C HK 5 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
145 Flow temperature SP at external temperature of +10°C HK 5 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
146 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
147 Desired room temperature during heating mode HK 6 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
148 Desired room temperature during setback mode HK 6 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
149 Controller gain room temperature Kp-Rm HK 6 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
150 Reduction of flow temperature in setback mode HK 6 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
151 External temperature HK 6 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
152 External temperature HK 6 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
153 Maximum flow temperature HK 6 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
154 Proportional factor for mixer control HK 6 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
155 Controller reset time HK 6 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
156 Mixer runtime HK 6 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
157 Frost protection temperature HK 6 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
158 Flow temperature SP at external temperature of -10°C HK 6 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
159 Flow temperature SP at external temperature of +10°C HK 6 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
160 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
161 Desired room temperature during heating mode HK 7 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
162 Desired room temperature during setback mode HK 7 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
163 Controller gain room temperature Kp-Rm HK 7 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
164 Reduction of flow temperature in setback mode HK 7 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
165 External temperature HK 7 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
166 External temperature HK 7 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
167 Maximum flow temperature HK 7 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
168 Proportional factor for mixer control HK 7 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
169 Controller reset time HK 7 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
170 Mixer runtime HK 7 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
171 Frost protection temperature HK 7 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
172 Flow temperature SP at external temperature of -10°C HK 7 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
173 Flow temperature SP at external temperature of +10°C HK 7 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
174 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
175 Desired room temperature during heating mode HK 8 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
176 Desired room temperature during setback mode HK 8 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
177 Controller gain room temperature Kp-Rm HK 8 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
178 Reduction of flow temperature in setback mode HK 8 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
179 External temperature HK 8 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
180 External temperature HK 8 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
181 Maximum flow temperature HK 8 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
182 Proportional factor for mixer control HK 8 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
183 Controller reset time HK 8 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
184 Mixer runtime HK 8 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
185 Frost protection temperature HK 8 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
186 Flow temperature SP at external temperature of -10°C HK 8 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
187 Flow temperature SP at external temperature of +10°C HK 8 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
188 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
189 Desired room temperature during heating mode HK 9 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
190 Desired room temperature during setback mode HK 9 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
191 Controller gain room temperature Kp-Rm HK 9 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
192 Reduction of flow temperature in setback mode HK 9 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
193 External temperature HK 9 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
194 External temperature HK 9 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
195 Maximum flow temperature HK 9 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
196 Proportional factor for mixer control HK 9 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
197 Controller reset time HK 9 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
198 Mixer runtime HK 9 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
199 Frost protection temperature HK 9 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
200 Flow temperature SP at external temperature of -10°C HK 9 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
201 Flow temperature SP at external temperature of +10°C HK 9 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
202 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
203 Desired room temperature during heating mode HK 10 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
204 Desired room temperature during setback mode HK 10 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
205 Controller gain room temperature Kp-Rm HK 10 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
206 Reduction of flow temperature in setback mode HK 10 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
207 External temperature HK 10 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
208 External temperature HK 10 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
209 Maximum flow temperature HK 10 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
210 Proportional factor for mixer control HK 10 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
211 Controller reset time HK 10 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
212 Mixer runtime HK 10 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
213 Frost protection temperature HK 10 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
214 Flow temperature SP at external temperature of -10°C HK 10 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
215 Flow temperature SP at external temperature of +10°C HK 10 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
216 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
217 Desired room temperature during heating mode HK 11 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
218 Desired room temperature during setback mode HK 11 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
219 Controller gain room temperature Kp-Rm HK 11 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
220 Reduction of flow temperature in setback mode HK 11 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
221 External temperature HK 11 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
222 External temperature HK 11 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
223 Maximum flow temperature HK 11 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
224 Proportional factor for mixer control HK 11 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
225 Controller reset time HK 11 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
226 Mixer runtime HK 11 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
227 Frost protection temperature HK 11 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
228 Flow temperature SP at external temperature of -10°C HK 11 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
229 Flow temperature SP at external temperature of +10°C HK 11 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
230 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
231 Desired room temperature during heating mode HK 12 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
232 Desired room temperature during setback mode HK 12 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
233 Controller gain room temperature Kp-Rm HK 12 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
234 Reduction of flow temperature in setback mode HK 12 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
235 External temperature HK 12 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
236 External temperature HK 12 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
237 Maximum flow temperature HK 12 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
238 Proportional factor for mixer control HK 12 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
239 Controller reset time HK 12 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
240 Mixer runtime HK 12 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
241 Frost protection temperature HK 12 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
242 Flow temperature SP at external temperature of -10°C HK 12 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
243 Flow temperature SP at external temperature of +10°C HK 12 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
244 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
245 Desired room temperature during heating mode HK 13 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
246 Desired room temperature during setback mode HK 13 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
247 Controller gain room temperature Kp-Rm HK 13 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
248 Reduction of flow temperature in setback mode HK 13 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
249 External temperature HK 13 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
250 External temperature HK 13 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
251 Maximum flow temperature HK 13 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
252 Proportional factor for mixer control HK 13 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
253 Controller reset time HK 13 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
254 Mixer runtime HK 13 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
255 Frost protection temperature HK 13 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
256 Flow temperature SP at external temperature of -10°C HK 13 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
257 Flow temperature SP at external temperature of +10°C HK 13 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
258 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
259 Desired room temperature during heating mode HK 14 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
260 Desired room temperature during setback mode HK 14 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
261 Controller gain room temperature Kp-Rm HK 14 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
262 Reduction of flow temperature in setback mode HK 14 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
263 External temperature HK 14 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
264 External temperature HK 14 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
265 Maximum flow temperature HK 14 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
266 Proportional factor for mixer control HK 14 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
267 Controller reset time HK 14 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
268 Mixer runtime HK 14 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
269 Frost protection temperature HK 14 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
270 Flow temperature SP at external temperature of -10°C HK 14 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
271 Flow temperature SP at external temperature of +10°C HK 14 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
272 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
273 Desired room temperature during heating mode HK 15 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
274 Desired room temperature during setback mode HK 15 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
275 Controller gain room temperature Kp-Rm HK 15 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
276 Reduction of flow temperature in setback mode HK 15 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
277 External temperature HK 15 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
278 External temperature HK 15 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
279 Maximum flow temperature HK 15 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
280 Proportional factor for mixer control HK 15 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
281 Controller reset time HK 15 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
282 Mixer runtime HK 15 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
283 Frost protection temperature HK 15 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
284 Flow temperature SP at external temperature of -10°C HK 15 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
285 Flow temperature SP at external temperature of +10°C HK 15 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
286 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
287 Desired room temperature during heating mode HK 16 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
288 Desired room temperature during setback mode HK 16 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
289 Controller gain room temperature Kp-Rm HK 16 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
290 Reduction of flow temperature in setback mode HK 16 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
291 External temperature HK 16 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
292 External temperature HK 16 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
293 Maximum flow temperature HK 16 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
294 Proportional factor for mixer control HK 16 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
295 Controller reset time HK 16 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
296 Mixer runtime HK 16 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
297 Frost protection temperature HK 16 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
298 Flow temperature SP at external temperature of -10°C HK 16 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
299 Flow temperature SP at external temperature of +10°C HK 16 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
300 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
301 Desired room temperature during heating mode HK 17 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
302 Desired room temperature during setback mode HK 17 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
303 Controller gain room temperature Kp-Rm HK 17 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
304 Reduction of flow temperature in setback mode HK 17 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
305 External temperature HK 17 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
306 External temperature HK 17 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
307 Maximum flow temperature HK 17 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
308 Proportional factor for mixer control HK 17 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
309 Controller reset time HK 17 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
310 Mixer runtime HK 17 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
311 Frost protection temperature HK 17 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
312 Flow temperature SP at external temperature of -10°C HK 17 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
313 Flow temperature SP at external temperature of +10°C HK 17 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
314 °C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
315 Desired room temperature during heating mode HK 18 °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
316 Desired room temperature during setback mode HK 18 °C 16.0 2013-12-27 10:28:14 (GMT-5) 16.0 2013-12-27 10:28:22 (GMT-5)
317 Controller gain room temperature Kp-Rm HK 18 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
318 Reduction of flow temperature in setback mode HK 18 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
319 External temperature HK 18 °C 18.0 2013-12-27 10:28:14 (GMT-5) 18.0 2013-12-27 10:28:22 (GMT-5)
320 External temperature HK 18 °C 7.0 2013-12-27 10:28:14 (GMT-5) 7.0 2013-12-27 10:28:22 (GMT-5)
321 Maximum flow temperature HK 18 °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
322 Proportional factor for mixer control HK 18 0.5 2013-12-27 10:28:14 (GMT-5) 0.5 2013-12-27 10:28:22 (GMT-5)
323 Controller reset time HK 18 s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
324 Mixer runtime HK 18 s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
325 Frost protection temperature HK 18 °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
326 Flow temperature SP at external temperature of -10°C HK 18 °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
327 Flow temperature SP at external temperature of +10°C HK 18 °C 40.0 2013-12-27 10:28:14 (GMT-5) 40.0 2013-12-27 10:28:22 (GMT-5)
328 Display CONF / NOT Used 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
329 Display CONF / NOT Used 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
330 Function of Control at Address 1 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
331 Function of Control at Address 2 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
332 Function of Control at Address 3 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
333 Function of Control at Address 4 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
334 Function of Control at Address 5 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
335 Function of Control at Address 6 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
336 Function of Control at Address 7 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
337 Flue gas temperature, below which boiler switches to SHUTDOWN status °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 2013-12-27 10:28:22 (GMT-5)
338 Primary air during heating-cleaning (absolute) % 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
339 Load if temperature difference between storage tank and DHW tank is Boiler 1 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
340 Set DHW temperature Boiler 1 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
341 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
342 Residual heat use Boiler 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
343 Reload if DHW tank temperature is below Boiler 1 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
344 Only load DHW tank once a day Boiler 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
345 Legionella heating activated Boiler 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
346 Which day for legionella heating Boiler 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
347 Load if temperature difference between boiler and DHW tank is Boiler 1 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
348 Setpoint for temperature difference between boiler - DHW tank Boiler 1 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
349 Controller gain DHW pump Kp-Bo Boiler 1 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
350 Controller reset time DHW tank pump Tn-Bo Boiler 1 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
351 Minimum DHW tank speed Boiler 1 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
352 Load if temperature difference between storage tank and DHW tank is Boiler 2 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
353 Set DHW temperature Boiler 2 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
354 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
355 Residual heat use Boiler 2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
356 Reload if DHW tank temperature is below Boiler 2 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
357 Only load DHW tank once a day Boiler 2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
358 Legionella heating activated Boiler 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
359 Which day for legionella heating Boiler 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
360 Load if temperature difference between boiler and DHW tank is Boiler 2 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
361 Setpoint for temperature difference between boiler - DHW tank Boiler 2 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
362 Controller gain DHW pump Kp-Bo Boiler 2 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
363 Controller reset time DHW tank pump Tn-Bo Boiler 2 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
364 Minimum DHW tank speed Boiler 2 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
365 Load if temperature difference between storage tank and DHW tank is Boiler 3 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
366 Set DHW temperature Boiler 3 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
367 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
368 Residual heat use Boiler 3 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
369 Reload if DHW tank temperature is below Boiler 3 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
370 Only load DHW tank once a day Boiler 3 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
371 Legionella heating activated Boiler 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
372 Which day for legionella heating Boiler 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
373 Load if temperature difference between boiler and DHW tank is Boiler 3 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
374 Setpoint for temperature difference between boiler - DHW tank Boiler 3 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
375 Controller gain DHW pump Kp-Bo Boiler 3 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
376 Controller reset time DHW tank pump Tn-Bo Boiler 3 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
377 Minimum DHW tank speed Boiler 3 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
378 Load if temperature difference between storage tank and DHW tank is Boiler 4 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
379 Set DHW temperature Boiler 4 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
380 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 4 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
381 Residual heat use Boiler 4 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
382 Reload if DHW tank temperature is below Boiler 4 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
383 Only load DHW tank once a day Boiler 4 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
384 Legionella heating activated Boiler 4 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
385 Which day for legionella heating Boiler 4 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
386 Load if temperature difference between boiler and DHW tank is Boiler 4 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
387 Setpoint for temperature difference between boiler - DHW tank Boiler 4 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
388 Controller gain DHW pump Kp-Bo Boiler 4 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
389 Controller reset time DHW tank pump Tn-Bo Boiler 4 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
390 Minimum DHW tank speed Boiler 4 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
391 Load if temperature difference between storage tank and DHW tank is Boiler 5 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
392 Set DHW temperature Boiler 5 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
393 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 5 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
394 Residual heat use Boiler 5 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
395 Reload if DHW tank temperature is below Boiler 5 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
396 Only load DHW tank once a day Boiler 5 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
397 Legionella heating activated Boiler 5 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
398 Which day for legionella heating Boiler 5 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
399 Load if temperature difference between boiler and DHW tank is Boiler 5 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
400 Setpoint for temperature difference between boiler - DHW tank Boiler 5 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
401 Controller gain DHW pump Kp-Bo Boiler 5 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
402 Controller reset time DHW tank pump Tn-Bo Boiler 5 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
403 Minimum DHW tank speed Boiler 5 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
404 Load if temperature difference between storage tank and DHW tank is Boiler 6 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
405 Set DHW temperature Boiler 6 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
406 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 6 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
407 Residual heat use Boiler 6 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
408 Reload if DHW tank temperature is below Boiler 6 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
409 Only load DHW tank once a day Boiler 6 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
410 Legionella heating activated Boiler 6 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
411 Which day for legionella heating Boiler 6 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
412 Load if temperature difference between boiler and DHW tank is Boiler 6 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
413 Setpoint for temperature difference between boiler - DHW tank Boiler 6 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
414 Controller gain DHW pump Kp-Bo Boiler 6 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
415 Controller reset time DHW tank pump Tn-Bo Boiler 6 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
416 Minimum DHW tank speed Boiler 6 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
417 Load if temperature difference between storage tank and DHW tank is Boiler 7 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
418 Set DHW temperature Boiler 7 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
419 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 7 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
420 Residual heat use Boiler 7 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
421 Reload if DHW tank temperature is below Boiler 7 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
422 Only load DHW tank once a day Boiler 7 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
423 Legionella heating activated Boiler 7 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
424 Which day for legionella heating Boiler 7 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
425 Load if temperature difference between boiler and DHW tank is Boiler 7 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
426 Setpoint for temperature difference between boiler - DHW tank Boiler 7 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
427 Controller gain DHW pump Kp-Bo Boiler 7 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
428 Controller reset time DHW tank pump Tn-Bo Boiler 7 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
429 Minimum DHW tank speed Boiler 7 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
430 Load if temperature difference between storage tank and DHW tank is Boiler 8 Δ°C 6.0 2013-12-27 10:28:14 (GMT-5) 6.0 2013-12-27 10:28:22 (GMT-5)
431 Set DHW temperature Boiler 8 °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
432 Which storage tank or heat distributor supplies the heat (0 = boiler) Boiler 8 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
433 Residual heat use Boiler 8 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
434 Reload if DHW tank temperature is below Boiler 8 Δ°C 45.0 2013-12-27 10:28:14 (GMT-5) 45.0 2013-12-27 10:28:22 (GMT-5)
435 Only load DHW tank once a day Boiler 8 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
436 Legionella heating activated Boiler 8 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
437 Which day for legionella heating Boiler 8 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
438 Load if temperature difference between boiler and DHW tank is Boiler 8 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
439 Setpoint for temperature difference between boiler - DHW tank Boiler 8 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
440 Controller gain DHW pump Kp-Bo Boiler 8 5.00 2013-12-27 10:28:14 (GMT-5) 5.00 2013-12-27 10:28:22 (GMT-5)
441 Controller reset time DHW tank pump Tn-Bo Boiler 8 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
442 Minimum DHW tank speed Boiler 8 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
443 Which second Boiler is installed? 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
444 Heating circuit release from following storage tank temperature Tank 1 °C 35.0 2013-12-27 10:28:14 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
445 Residual heat use Tank 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
446 Temperature difference between boiler and border layer Tank 1 Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
447 Minimum storage tank pump speed Tank 1 % 60 2014-03-06 10:34:12 (GMT-5) 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
448 Controller gain for storage tank pump Kp-Pu Tank 1 2.50 2013-12-27 10:28:14 (GMT-5) 2.50 2013-12-27 10:28:22 (GMT-5)
449 Controller reset time Tank 1 s 600 2013-12-27 10:28:14 (GMT-5) 600 2014-01-10 08:48:11 (GMT-5) 500 2013-12-27 10:28:22 (GMT-5)
450 Top storage tank minimum temperature - startup point Tank 1 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
451 storage tank fully loaded if temperature difference between boiler and bottom storage tank Tank 1 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
452 Heating circuit release from following storage tank temperature Tank 2 °C 30.0 2013-12-27 10:28:14 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
453 Residual heat use Tank 2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
454 Temperature difference between boiler and border layer Tank 2 Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
455 Minimum storage tank pump speed Tank 2 % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
456 Controller gain for storage tank pump Kp-Pu Tank 2 2.50 2013-12-27 10:28:14 (GMT-5) 2.50 2013-12-27 10:28:22 (GMT-5)
457 Controller reset time Tank 2 s 600 2013-12-27 10:28:14 (GMT-5) 600 2013-12-27 10:28:22 (GMT-5)
458 Top storage tank minimum temperature - startup point Tank 2 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
459 storage tank fully loaded if temperature difference between boiler and bottom storage tank Tank 2 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
460 Heating circuit release from following storage tank temperature Tank 3 °C 30.0 2013-12-27 10:28:14 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
461 Residual heat use Tank 3 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
462 Temperature difference between boiler and border layer Tank 3 Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
463 Minimum storage tank pump speed Tank 3 % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
464 Controller gain for storage tank pump Kp-Pu Tank 3 2.50 2013-12-27 10:28:14 (GMT-5) 2.50 2013-12-27 10:28:22 (GMT-5)
465 Controller reset time Tank 3 s 600 2013-12-27 10:28:14 (GMT-5) 600 2013-12-27 10:28:22 (GMT-5)
466 Top storage tank minimum temperature - startup point Tank 3 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
467 storage tank fully loaded if temperature difference between boiler and bottom storage tank Tank 3 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
468 Heating circuit release from following storage tank temperature Tank 4 °C 30.0 2013-12-27 10:28:14 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
469 Residual heat use Tank 4 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
470 Temperature difference between boiler and border layer Tank 4 Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
471 Minimum storage tank pump speed Tank 4 % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
472 Controller gain for storage tank pump Kp-Pu Tank 4 2.50 2013-12-27 10:28:14 (GMT-5) 2.50 2013-12-27 10:28:22 (GMT-5)
473 Controller reset time Tank 4 s 600 2013-12-27 10:28:14 (GMT-5) 600 2013-12-27 10:28:22 (GMT-5)
474 Top storage tank minimum temperature - startup point Tank 4 Δ°C 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
475 storage tank fully loaded if temperature difference between boiler and bottom storage tank Tank 4 Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
476 Cycle of ash screw s 1000 2013-12-27 10:28:14 (GMT-5) 1000 2013-12-27 10:28:22 (GMT-5)
477 Runtime of the ash screw s 70 2013-12-27 10:28:14 (GMT-5) 70 2013-12-27 10:28:22 (GMT-5)
478 First start of cleaning h 8.00 2013-12-27 10:28:14 (GMT-5) 8.00 2013-12-27 10:28:22 (GMT-5)
479 Second start of cleaning h 15.00 2013-12-27 10:28:14 (GMT-5) 15.00 2013-12-27 10:28:22 (GMT-5)
480 Modem installed 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
481 Boiler temperature setpoint °C 74.0 2014-03-06 10:32:05 (GMT-5) 80.0 2014-01-24 10:02:54 (GMT-5) 74.0 2014-03-06 10:37:25 (GMT-5) 80.0 2014-01-24 10:05:59 (GMT-5)
482 Minimum boiler temperature to release all pumps °C 50.0 2014-03-06 10:32:05 (GMT-5) 35.0 2013-12-27 10:28:14 (GMT-5) 60.0 2014-03-06 10:37:25 (GMT-5) 35.0 2014-01-24 10:07:16 (GMT-5)
483 Maximum time until switching of probe m 20 2013-12-27 10:28:14 (GMT-5) 20 2014-01-24 09:55:55 (GMT-5) 10 2014-01-10 08:48:11 (GMT-5)
484 Standby boiler start delay m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
485 Standby boiler start °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
486 Standby boiler minimum runtime m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
487 Minimum temperature of standby boiler °C 55.0 2013-12-27 10:28:14 (GMT-5) 55.0 2013-12-27 10:28:22 (GMT-5)
488 Temperature difference between standby boiler and storage tank Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
489 Solar system 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
490 Temp differential to start collector pump Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
491 Temp difference to stop collector pump Δ°C 5.0 2013-12-27 10:28:14 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
492 Maximum storage tank bottom temperature during solar charging °C 85.0 2013-12-27 10:28:14 (GMT-5) 85.0 2013-12-27 10:28:22 (GMT-5)
493 Boiler target temperature during solar charging °C 75.0 2013-12-27 10:28:14 (GMT-5) 75.0 2013-12-27 10:28:22 (GMT-5)
494 Minimum collector pump speed % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
495 Which sensor is used for standby boiler 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
496 Which sensor is used for storage tank top Tank 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
497 Which sensor is used for middle storage tank Tank 1 4 2013-12-27 10:28:14 (GMT-5) 6 2013-12-27 10:28:22 (GMT-5)
498 Which sensor is used for bottom storage tank Tank 1 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
499 Which sensor is used for top DHW tank 1 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
500 Which sensor is used for bottom DHW tank 1 4 2013-12-27 10:28:14 (GMT-5) 4 2013-12-27 10:28:22 (GMT-5)
501 Which sensor is used for the solar collector 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
502 Which sensor is used for the storage tank reference 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
503 Which pump is used for the solar collector 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
504 Which output is used for unloading follow-up boiler 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
505 Secondary air at door open (0% deactivated) % 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
506 ID fan output at open door (default 100%) % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
507 Which pump is used for the solar isolating valve 18 2013-12-27 10:28:14 (GMT-5) 18 2013-12-27 10:28:22 (GMT-5)
508 Which pump is used for DHW tank 1 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
509 Controller gain for ID fan controller Kp 0.70 2013-12-27 10:28:14 (GMT-5) 0.70 2013-12-27 10:28:22 (GMT-5)
510 Reset time for ID fan regulator Tn s 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
511 Clean after how many shutdowns/T4: Tilt Grate How Often During Cleaning 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
512 Minimum flue gas temperature °C 90.0 2013-12-27 10:28:14 (GMT-5) 90.0 2013-12-27 10:28:22 (GMT-5)
513 residual oxygen content setpoint % 8.0 2013-12-27 10:28:14 (GMT-5) 8.0 2013-12-27 10:28:22 (GMT-5)
514 Temperature in the hi-limit stat housing at which all pumps run °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 2013-12-27 10:28:22 (GMT-5)
515 Maximum current for delivery screw A 3.50 2013-12-27 10:28:14 (GMT-5) 3.50 2013-12-27 10:28:22 (GMT-5)
516 Pause before cleaning/During heating-cleaning reduce output for m 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
517 Start of 2nd pellet filling h 4.50 2014-01-24 09:45:40 (GMT-5) 17.00 2013-12-27 10:28:14 (GMT-5) 2.50 2014-01-24 09:53:54 (GMT-5) 18.12 2014-01-10 08:49:11 (GMT-5)
518 Fuel Selected (32=chips; 34,73=pellets) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
519 Max. runtime of suction fan m 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
520 Should this heating circuit heat when there is DHW boiler priority ? HK 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
521 Should this heating circuit heat when there is DHW boiler priority ? HK 2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
522 Should this heating circuit heat when there is DHW boiler priority ? HK 3 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
523 Should this heating circuit heat when there is DHW boiler priority ? HK 4 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
524 Should this heating circuit heat when there is DHW boiler priority ? HK 5 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
525 Should this heating circuit heat when there is DHW boiler priority ? HK 6 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
526 Should this heating circuit heat when there is DHW boiler priority ? HK 7 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
527 Should this heating circuit heat when there is DHW boiler priority ? HK 8 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
528 Should this heating circuit heat when there is DHW boiler priority ? HK 9 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
529 Should this heating circuit heat when there is DHW boiler priority ? HK 10 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
530 Should this heating circuit heat when there is DHW boiler priority ? HK 11 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
531 Should this heating circuit heat when there is DHW boiler priority ? HK 12 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
532 Should this heating circuit heat when there is DHW boiler priority ? HK 13 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
533 Should this heating circuit heat when there is DHW boiler priority ? HK 14 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
534 Should this heating circuit heat when there is DHW boiler priority ? HK 15 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
535 Should this heating circuit heat when there is DHW boiler priority ? HK 16 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
536 Should this heating circuit heat when there is DHW boiler priority ? HK 17 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
537 Should this heating circuit heat when there is DHW boiler priority ? HK 18 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
538 Which sensor is used for top DHW tank 2 19 2013-12-27 10:28:14 (GMT-5) 19 2013-12-27 10:28:22 (GMT-5)
539 Which sensor is used for bottom DHW tank 2 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
540 Which pump is used for DHW tank 2 18 2013-12-27 10:28:14 (GMT-5) 18 2013-12-27 10:28:22 (GMT-5)
541 Which sensor is used for top DHW tank 3 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
542 Which sensor is used for bottom DHW tank 3 36 2013-12-27 10:28:14 (GMT-5) 36 2013-12-27 10:28:22 (GMT-5)
543 Which pump is used for DHW tank 3 34 2013-12-27 10:28:14 (GMT-5) 34 2013-12-27 10:28:22 (GMT-5)
544 Which sensor is used for top DHW tank 4 51 2013-12-27 10:28:14 (GMT-5) 51 2013-12-27 10:28:22 (GMT-5)
545 Which sensor is used for bottom DHW tank 4 52 2013-12-27 10:28:14 (GMT-5) 52 2013-12-27 10:28:22 (GMT-5)
546 Which pump is used for DHW tank 4 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
547 Which sensor is used for top DHW tank 5 67 2013-12-27 10:28:14 (GMT-5) 67 2013-12-27 10:28:22 (GMT-5)
548 Which sensor is used for bottom DHW tank 5 68 2013-12-27 10:28:14 (GMT-5) 68 2013-12-27 10:28:22 (GMT-5)
549 Which pump is used for DHW tank 5 66 2013-12-27 10:28:14 (GMT-5) 66 2013-12-27 10:28:22 (GMT-5)
550 Which sensor is used for top DHW tank 6 83 2013-12-27 10:28:14 (GMT-5) 83 2013-12-27 10:28:22 (GMT-5)
551 Which sensor is used for bottom DHW tank 6 84 2013-12-27 10:28:14 (GMT-5) 84 2013-12-27 10:28:22 (GMT-5)
552 Which pump is used for DHW tank 6 82 2013-12-27 10:28:14 (GMT-5) 82 2013-12-27 10:28:22 (GMT-5)
553 Which sensor is used for top DHW tank 7 99 2013-12-27 10:28:14 (GMT-5) 99 2013-12-27 10:28:22 (GMT-5)
554 Which sensor is used for bottom DHW tank 7 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
555 Which pump is used for DHW tank 7 98 2013-12-27 10:28:14 (GMT-5) 98 2013-12-27 10:28:22 (GMT-5)
556 Which sensor is used for top DHW tank 8 115 2013-12-27 10:28:14 (GMT-5) 115 2013-12-27 10:28:22 (GMT-5)
557 Which sensor is used for bottom DHW tank 8 116 2013-12-27 10:28:14 (GMT-5) 116 2013-12-27 10:28:22 (GMT-5)
558 Which pump is used for DHW tank 8 114 2013-12-27 10:28:14 (GMT-5) 114 2013-12-27 10:28:22 (GMT-5)
559 Suction fan run-on s 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
560 Delivery screw runtime s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
561 Delivery screw pause time s 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
562 Minimum combustion chamber temperature °C 600.0 2013-12-27 10:28:14 (GMT-5) 600.0 2013-12-27 10:28:22 (GMT-5)
563 Maximum combustion chamber temperature °C 900.0 2013-12-27 10:28:14 (GMT-5) 900.0 2013-12-27 10:28:22 (GMT-5)
564 Delay of secondary air control s 200 2013-12-27 10:28:14 (GMT-5) 200 2013-12-27 10:28:22 (GMT-5)
565 Delay of primary air control s 200 2013-12-27 10:28:14 (GMT-5) 200 2013-12-27 10:28:22 (GMT-5)
566 During heating - cleaning the grate should stay open for s 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
567 NO feed if temp over °C 1050.0 2013-12-27 10:28:14 (GMT-5) 1050.0 2013-12-27 10:28:22 (GMT-5)
568 Minimum lambda control fan speed % 85 2013-12-27 10:28:14 (GMT-5) 85 2013-12-27 10:28:22 (GMT-5)
569 Minimum fan speed of combustion chamber controller % 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
570 Maximum feed correction by O2 controller % 0.2 2013-12-27 10:28:14 (GMT-5) 0.2 2013-12-27 10:28:22 (GMT-5)
571 Primary air delay s 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
572 primary air boost during heating up % 25 2013-12-27 10:28:14 (GMT-5) 25 2013-12-27 10:28:22 (GMT-5)
573 Duration of primary air boost m 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
574 Maximal deviation of residual O2 from setpoint/T4: O2 setpoint increase for partial load % 1.0 2013-12-27 10:28:14 (GMT-5) 1.0 2013-12-27 10:28:22 (GMT-5)
575 Permitted start processes with blocked ash screw 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
576 Feed correction controller gain 0.20 2013-12-27 10:28:14 (GMT-5) 0.20 2013-12-27 10:28:22 (GMT-5)
577 Reset time for feed correction controller 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
578 Boiler underpressure setpoint at max output P 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
579 ID fan startup time/T4: Duration of Preparation s 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
580 Under-pressure MIN control variable % 25 2013-12-27 10:28:14 (GMT-5) 25 2013-12-27 10:28:22 (GMT-5)
581 Under-pressure controller gain 0.30 2013-12-27 10:28:14 (GMT-5) 0.30 2013-12-27 10:28:22 (GMT-5)
582 Under-pressure controller reset time s 25 2013-12-27 10:28:14 (GMT-5) 25 2013-12-27 10:28:22 (GMT-5)
583 Stoker pre-run/T4: Min Feed Time of Feed Screw s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
584 Feed time of feed screw is s 5.0 2013-12-27 10:28:14 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
585 Tip the grate how often during heating-cleaning? 350 2013-12-27 10:28:14 (GMT-5) 350 2013-12-27 10:28:22 (GMT-5)
586 How long should I vibrate/T4: Activation delay for slide-in s 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
587 After what charge time s 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
588 WOS start time h 9.00 2013-12-27 10:28:14 (GMT-5) 9.00 2013-12-27 10:28:22 (GMT-5)
589 WOS stop time h 22.00 2013-12-27 10:28:14 (GMT-5) 22.00 2013-12-27 10:28:22 (GMT-5)
590 WOS runs every s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
591 Feed time until there is a fuel quantity suitable for ignition s 80 2013-12-27 10:28:14 (GMT-5) 80 2013-12-27 10:28:22 (GMT-5)
592 The time until the stoker is empty is s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
593 primary air boost during shutdown/T4: Min opening of air flap at full load % 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
594 Automatic ignition 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
595 Start ignition 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
596 s 54 2013-12-27 10:28:14 (GMT-5) 54 2013-12-27 10:28:22 (GMT-5)
597 Rotary valve run-on 30.0 2013-12-27 10:28:14 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
598 Counter limit for troubleshooting of stoker overcurrent is 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
599 Counter limit for troubleshooting of feed screw overcurrent is 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
600 Counter limit for troubleshooting of rotary valve overcurrent is 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
601 During troubleshooting of stoker, it turns forwards for s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
602 During troubleshooting of stoker, it turns backwards for s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
603 A stoker motor protection switch error is delayed for s 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
604 During troubleshooting of feed screw, it turns forwards for s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
605 During troubleshooting of feed screw, it turns backwards for s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
606 A feed screw motor protection switch error is delayed for s 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
607 During troubleshooting of rotary valve s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
608 During troubleshooting of rotary valve s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
609 A rotary valve motor protection switch error is delayed for s 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
610 The back-burn flap opens after a maximum of s 150 2013-12-27 10:28:14 (GMT-5) 150 2013-12-27 10:28:22 (GMT-5)
611 The back-burn flap closes after a maximum of s 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
612 Nominal current for stoker screw A 1.10 2013-12-27 10:28:14 (GMT-5) 1.10 2013-12-27 10:28:22 (GMT-5)
613 Nominal current for feed screw A 1.60 2013-12-27 10:28:14 (GMT-5) 1.60 2013-12-27 10:28:22 (GMT-5)
614 A 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
615 Heating up time for lambda probe s 360 2013-12-27 10:28:14 (GMT-5) 360 2013-12-27 10:28:22 (GMT-5)
616 Vacuum filling system permitted from 1320 2013-12-27 10:28:14 (GMT-5) 1320 2013-12-27 10:28:22 (GMT-5)
617 Vacuum filling system permitted until 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
618 Ignition switches off above °C 100.0 2013-12-27 10:28:14 (GMT-5) 100.0 2013-12-27 10:28:22 (GMT-5)
619 Switch-on delay feed screw light barrier s 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
620 Error of light barrier(s) is delayed for s 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
621 Display with address 1 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
622 Display with address 2 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
623 Display with address 3 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
624 Display with address 4 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
625 Display with address 5 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
626 Display with address 6 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
627 Display with address 7 is allocated to the following heating circuit: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
628 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
629 Display with address 1 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
630 Display with address 2 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
631 Display with address 3 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
632 Display with address 4 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
633 Display with address 5 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
634 Display with address 6 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
635 Display with address 7 is allocated to the following DHW tank: 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
636 slide valve installed on pellet cyclone 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
637 minimum output % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
638 Maximum boost of output to % 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
639 Is a PT1000 sensor used as a solar sensor? 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
640 ID fan at 0% secondary air (lower point of ID fan controller) % 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
641 Activate ID fan controller/T4: Cleaning after standby 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
642 The time until the stoker is full is s 70 2013-12-27 10:28:14 (GMT-5) 70 2013-12-27 10:28:22 (GMT-5)
643 Minimum loading rate % 12 2013-12-27 10:28:14 (GMT-5) 12 2013-12-27 10:28:22 (GMT-5)
644 ID fan offset % 10 2013-12-27 10:28:14 (GMT-5) 0 2014-01-10 08:48:11 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
645 Which pump is used for the storage tank Tank 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
646 Maximum fan speed in firewood mode % 80 2013-12-27 10:28:14 (GMT-5) 80 2013-12-27 10:28:22 (GMT-5)
647 Which sensor is used for the network return temperature 6 2013-12-27 10:28:14 (GMT-5) 6 2013-12-27 10:28:22 (GMT-5)
648 Network return setpoint °C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
649 Minimum speed for network pump % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
650 Which pump is used for the network pump 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
651 In blower fan run-on the shaker should run for s 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
652 In blower fan run-on the shaker should switch on every s 15 2013-12-27 10:28:14 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
653 Ignition time ( date - time ) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
654 540 2013-12-27 10:28:14 (GMT-5) 540 2013-12-27 10:28:22 (GMT-5)
655 Start ignition 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
656 Output co-efficient for specified boiler s 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
657 Delay of secondary air cooling at decreasing cc temp signal s 15 2013-12-27 10:28:14 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
658 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
659 Adopt specified boiler values 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
660 Adopt specified material values 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
661 Maximum ID fan speed % 95 2013-12-27 10:28:14 (GMT-5) 95 2013-12-27 10:28:22 (GMT-5)
662 P4 Pellet 32/38 with small cyclone installed 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
663 Memory cycle of data logger s 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
664 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
665 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
666 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
667 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 4 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
668 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 5 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
669 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 6 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
670 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 7 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
671 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 8 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
672 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 9 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
673 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 10 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
674 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 11 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
675 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 12 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
676 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 13 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
677 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 14 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
678 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 15 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
679 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 16 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
680 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 17 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
681 From which storage tank or distributor is the heating circuit supplied (0 = boiler) HK 18 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
682 Which sensor is used for feeder 1 22 2013-12-27 10:28:14 (GMT-5) 22 2013-12-27 10:28:22 (GMT-5)
683 Which sensor is used for feeder 2 38 2013-12-27 10:28:14 (GMT-5) 38 2013-12-27 10:28:22 (GMT-5)
684 Which sensor is used for feeder 3 54 2013-12-27 10:28:14 (GMT-5) 54 2013-12-27 10:28:22 (GMT-5)
685 Which sensor is used for feeder 4 70 2013-12-27 10:28:14 (GMT-5) 70 2013-12-27 10:28:22 (GMT-5)
686 Which pump is used for feeder 1 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
687 Which pump is used for feeder 2 33 2013-12-27 10:28:14 (GMT-5) 33 2013-12-27 10:28:22 (GMT-5)
688 Which pump is used for feeder 3 49 2013-12-27 10:28:14 (GMT-5) 49 2013-12-27 10:28:22 (GMT-5)
689 Which pump is used for feeder 4 65 2013-12-27 10:28:14 (GMT-5) 65 2013-12-27 10:28:22 (GMT-5)
690 Return temperature setpoint feeder 1 °C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
691 Return temperature setpoint feeder 2 °C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
692 Return temperature setpoint feeder 3 °C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
693 Return temperature setpoint feeder 4 °C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
694 Minimum speed for feeder pump 1 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
695 Minimum speed for feeder pump 2 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
696 Minimum speed for feeder pump 3 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
697 Minimum speed for feeder pump 4 % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
698 Maximum loading rate % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
699 QC_o2_max_Kp/T4: Gain for O2 controller Kp 0.50 2013-12-27 10:28:14 (GMT-5) 0.50 2013-12-27 10:28:22 (GMT-5)
700 QC_o2_max_Tn/T4: Reset Time for O2 regulator Tn s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
701 Under-pressure at minimum output P 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
702 TC_fr_min_Kp/T4: Time until stoker is full s 55 2013-12-27 10:28:14 (GMT-5) 55 2013-12-27 10:28:22 (GMT-5)
703 The time until the stoker is full is/T4:Feed time until there is a fuel quantity suitable for ignition s 12 2013-12-27 10:28:14 (GMT-5) 12 2013-12-27 10:28:22 (GMT-5)
704 Feed time until there is a fuel quantity suitable for ignition/T4: Time until stoker is empty s 55 2013-12-27 10:28:14 (GMT-5) 55 2013-12-27 10:28:22 (GMT-5)
705 The time until the stoker is empty is s 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
706 Switch-off delay feed screw light barrier s 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
707 Switch-off delay of delivery screw(s) light barrier(s) s 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
708 Switch-on delay of delivery screw(s) light barrier(s) % 74 2013-12-27 10:28:14 (GMT-5) 70 2014-01-10 08:48:11 (GMT-5) 75 2013-12-27 10:28:22 (GMT-5)
709 Minimum path for slide valve % 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
710 O2 setpoint increase for half load % 3.0 2013-12-27 10:28:14 (GMT-5) 3.0 2013-12-27 10:28:22 (GMT-5)
711 O2 setpoint increase for partial load % 65 2013-12-27 10:28:14 (GMT-5) 65 2013-12-27 10:28:22 (GMT-5)
712 O2 setpoint increase start of half load % 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
713 O2 setpoint increase start of partial load % 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
714 O2 controller max reduction for half load % 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
715 O2 controller max reduction for partial load % 65 2013-12-27 10:28:14 (GMT-5) 65 2013-12-27 10:28:22 (GMT-5)
716 O2 controller max reduction start of half load % 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
717 O2 controller max reduction start of partial load % 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
718 O2 setpoint + value of monitoring limit s 420 2013-12-27 10:28:14 (GMT-5) 420 2013-12-27 10:28:22 (GMT-5)
719 During heating-cleaning release output after m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
720 Air quantity that should be reached during preparation with P4 Pellet 8/15 mV 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
721 Air quantity m 0.20 2013-12-27 10:28:14 (GMT-5) 0.20 2013-12-27 10:28:22 (GMT-5)
722 Maximum deviation from air quantity during preparation s 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
723 Filter constant for actual O2 monitoring m 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
724 Start delay for O2 monitoring 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
725 Minimum fan speed in firewood mode % 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
726 Minimum fan speed in firewood mode for ID fan speed % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
727 Monitoring window (sec) for feed and boiler control variable s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
728 Oil valve shut delay s 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
729 O2 monitoring active 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
730 Which sensor is used for the heat source DRA 117 2013-12-27 10:28:14 (GMT-5) 117 2013-12-27 10:28:22 (GMT-5)
731 Which sensor is used for the heat sink DRA 118 2013-12-27 10:28:14 (GMT-5) 118 2013-12-27 10:28:22 (GMT-5)
732 Minimum pump speed DRA % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
733 Startup difference DRA Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
734 Shutdown difference DRA Δ°C 5.0 2013-12-27 10:28:14 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
735 Which pump is used DRA 114 2013-12-27 10:28:14 (GMT-5) 114 2013-12-27 10:28:22 (GMT-5)
736 KP factor control DRA 2.00 2013-12-27 10:28:14 (GMT-5) 2.00 2013-12-27 10:28:22 (GMT-5)
737 TN value control DRA s 300 2013-12-27 10:28:14 (GMT-5) 300 2013-12-27 10:28:22 (GMT-5)
738 Reset troubleshooting time once 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
739 Air quantity to be reached during preparation m 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
740 Which sensor is used for storage tank top Tank 2 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
741 Which sensor is used for middle storage tank Tank 2 22 2013-12-27 10:28:14 (GMT-5) 22 2013-12-27 10:28:22 (GMT-5)
742 Which sensor is used for bottom storage tank Tank 2 18 2013-12-27 10:28:14 (GMT-5) 18 2013-12-27 10:28:22 (GMT-5)
743 Which pump is used for the storage tank Tank 2 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
744 Which sensor is used for storage tank top Tank 3 33 2013-12-27 10:28:14 (GMT-5) 33 2013-12-27 10:28:22 (GMT-5)
745 Which sensor is used for middle storage tank Tank 3 38 2013-12-27 10:28:14 (GMT-5) 38 2013-12-27 10:28:22 (GMT-5)
746 Which sensor is used for bottom storage tank Tank 3 34 2013-12-27 10:28:14 (GMT-5) 34 2013-12-27 10:28:22 (GMT-5)
747 Which pump is used for the storage tank Tank 3 33 2013-12-27 10:28:14 (GMT-5) 33 2013-12-27 10:28:22 (GMT-5)
748 Which sensor is used for storage tank top Tank 4 49 2013-12-27 10:28:14 (GMT-5) 49 2013-12-27 10:28:22 (GMT-5)
749 Which sensor is used for middle storage tank Tank 4 54 2013-12-27 10:28:14 (GMT-5) 54 2013-12-27 10:28:22 (GMT-5)
750 Which sensor is used for bottom storage tank Tank 4 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
751 Which pump is used for the storage tank Tank 4 49 2013-12-27 10:28:14 (GMT-5) 49 2013-12-27 10:28:22 (GMT-5)
752 Invert isolating valve 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
753 Switch off the pump at what return temperature in the circulation line °C 35.0 2013-12-27 10:28:14 (GMT-5) 35.0 2013-12-27 10:28:22 (GMT-5)
754 Circulation pump run-on s 300 2013-12-27 10:28:14 (GMT-5) 300 2013-12-27 10:28:22 (GMT-5)
755 Return sensor present 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
756 Which sensor is used for the circulation return 6 2013-12-27 10:28:14 (GMT-5) 6 2013-12-27 10:28:22 (GMT-5)
757 Which pump is used for the circulation 49 2013-12-27 10:28:14 (GMT-5) 49 2013-12-27 10:28:22 (GMT-5)
758 Mode (transition=2/winter=0...) 2 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
759 Invert standby boiler isolating valve 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
760 Minimum temperature for heat source °C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
761 Maximum temperature for heat sink °C 130.0 2013-12-27 10:28:14 (GMT-5) 130.0 2013-12-27 10:28:22 (GMT-5)
762 Which sensor is used for the heat exchanger sec. flow? 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
763 Which sensor is used for the collector return 21 2013-12-27 10:28:14 (GMT-5) 21 2013-12-27 10:28:22 (GMT-5)
764 s 120 2013-12-27 10:28:14 (GMT-5) 120 2013-12-27 10:28:22 (GMT-5)
765 Heat exchanger - storage tank pump stop delay s 240 2013-12-27 10:28:14 (GMT-5) 240 2013-12-27 10:28:22 (GMT-5)
766 Maximum collector pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
767 storage tank top solar setpoint (fast loading until this temperature) °C 60.0 2013-12-27 10:28:14 (GMT-5) 60.0 2013-12-27 10:28:22 (GMT-5)
768 Collector - storage tank top differential Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
769 Collector - heat exchanger sec. Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
770 Collector return - storage tank bottom differential Δ°C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
771 Collector pump control Kp value 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
772 Collector pump control Tn value s 300 2013-12-27 10:28:14 (GMT-5) 300 2013-12-27 10:28:22 (GMT-5)
773 Which pump is used for storage tank - heat exchanger 33 2013-12-27 10:28:14 (GMT-5) 33 2013-12-27 10:28:22 (GMT-5)
774 Which pump is used for DHW tank - heat exchanger 34 2013-12-27 10:28:14 (GMT-5) 34 2013-12-27 10:28:22 (GMT-5)
775 Control heating circuit according to program (NO -> heating circuit is switched off) HK 1 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
776 Control heating circuit according to program (NO -> heating circuit is switched off) HK 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
777 Control heating circuit according to program (NO -> heating circuit is switched off) HK 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
778 Control heating circuit according to program (NO -> heating circuit is switched off) HK 4 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
779 8 2013-12-27 10:28:14 (GMT-5) 8 2013-12-27 10:28:22 (GMT-5)
780 P4 Boiler Type 8 2013-12-27 10:28:14 (GMT-5) 8 2013-12-27 10:28:22 (GMT-5)
781 S4 Boiler Type 16 2013-12-27 10:28:14 (GMT-5) 16 2013-12-27 10:28:22 (GMT-5)
782 Which sensor input is used for the flow switch 21 2013-12-27 10:28:14 (GMT-5) 21 2013-12-27 10:28:22 (GMT-5)
783 Air quantity m 2.00 2013-12-27 10:28:14 (GMT-5) 2.00 2013-12-27 10:28:22 (GMT-5)
784 Residual O2 after opening door (applies for dry material selection) % 15.0 2013-12-27 10:28:14 (GMT-5) 15.0 2013-12-27 10:28:22 (GMT-5)
785 Ramp after opening door for residual O2 [sec / 0.1%] s 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
786 Very dry material 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
787 Adopt boiler standard values 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
788 Lambda probe correction value 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
789 Control standby boiler variably to the target value 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
790 Standby boiler delivery temperature °C 95.0 2013-12-27 10:28:14 (GMT-5) 95.0 2013-12-27 10:28:22 (GMT-5)
791 Control heating circuit according to program (NO -> heating circuit is switched off) HK 5 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
792 Control heating circuit according to program (NO -> heating circuit is switched off) HK 6 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
793 Control heating circuit according to program (NO -> heating circuit is switched off) HK 7 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
794 Control heating circuit according to program (NO -> heating circuit is switched off) HK 8 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
795 Control heating circuit according to program (NO -> heating circuit is switched off) HK 9 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
796 Control heating circuit according to program (NO -> heating circuit is switched off) HK 10 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
797 Nominal flow of collector pump for heat meter [L/h] 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
798 Room air independent operation 1 2013-12-27 10:28:14 (GMT-5) 0 2014-01-10 08:48:11 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
799 In pellet mode stop storage tank loading bec. of middle storage tank sensor 1 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
800 Collector monitoring -> Collector pump is switched on every 30 min. for 10 sec. 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
801 Output warnings through fault message relays 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
802 Condensation heat exchanger present (P4 Pellet) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
803 Clean after how many hours heating h 8.0 2013-12-27 10:28:14 (GMT-5) 8.0 2013-12-27 10:28:22 (GMT-5)
804 DHW tanks run-on (this setting applies for all DHW tanks) min 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
805 DHW tanks run-on (this setting applies for all DHW tanks) min 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
806 Width of the cc temp. control band Δ°C 50.0 2013-12-27 10:28:14 (GMT-5) 50.0 2013-12-27 10:28:22 (GMT-5)
807 Start of combustion chamber temperature control °C 600.0 2013-12-27 10:28:14 (GMT-5) 600.0 2013-12-27 10:28:22 (GMT-5)
808 Start of combustion chamber cooling at cc temp signal % 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
809 End of combustion chamber cooling at cc temp signal % 70 2013-12-27 10:28:14 (GMT-5) 70 2013-12-27 10:28:22 (GMT-5)
810 Start of slide-in reduction from cc temp signal % 25 2013-12-27 10:28:14 (GMT-5) 25 2013-12-27 10:28:22 (GMT-5)
811 Start emergency skimming from STL sensor temp. °C 102.0 2013-12-27 10:28:14 (GMT-5) 102.0 2013-12-27 10:28:22 (GMT-5)
812 Enable heating circuit pump 0 according to top store 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
813 Pump output for skimming P4 Pellet 113 2013-12-27 10:28:14 (GMT-5) 113 2013-12-27 10:28:22 (GMT-5)
814 PIN Code for Visualization (0 = Deactivated) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
815 Deviation of room sensor from display with address 1 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
816 Deviation of room sensor from display with address 2 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
817 Deviation of room sensor from display with address 3 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
818 Deviation of room sensor from display with address 4 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
819 Deviation of room sensor from display with address 5 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
820 Deviation of room sensor from display with address 6 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
821 Deviation of room sensor from display with address 7 Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
822 O2 control release in heating from min 5 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
823 If the boiler is active then all stores charge 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
824 Min. current monitoring with stoker 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
825 Heating hours until ash removal warning h 5000 2016-04-06 10:04:42 (GMT-5) 1000 2013-12-27 10:28:14 (GMT-5) 5000 2016-04-06 10:50:53 (GMT-5) 1000 2013-12-27 10:28:22 (GMT-5)
826 Desired work point of flue gas temperature °C 190.0 2013-12-27 10:28:14 (GMT-5) 190.0 2013-12-27 10:28:22 (GMT-5)
827 Flue gas work control Kp 1.00 2013-12-27 10:28:14 (GMT-5) 1.00 2013-12-27 10:28:22 (GMT-5)
828 Flue gas work control Tn s 350 2013-12-27 10:28:14 (GMT-5) 350 2013-12-27 10:28:22 (GMT-5)
829 Activate the ash screw at intervals during heating-cleaning 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
830 Store - Store difference Δ°C 2.0 2013-12-27 10:28:14 (GMT-5) 2.0 2013-12-27 10:28:22 (GMT-5)
831 For solar to store and DHW tank; the DHW tank has priority 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
832 Heating up program active 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
833 Current day of the heating up program 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
834 For which heating circuit should the program apply 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
835 Which heating up program is used 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
836 Which sensor is used for storage tank sensor 3 3 2013-12-27 10:28:14 (GMT-5) 4 2014-01-10 08:48:11 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
837 Output fire off message using HKP0 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
838 Return setpoint delay s 200 2013-12-27 10:28:14 (GMT-5) 200 2013-12-27 10:28:22 (GMT-5)
839 Return setpoint boost (power influence) % 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
840 Return feed lift min. dif. at min. output Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
841 Return feed lift min. dif. at 100% output Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
842 Buffer charge is 100 % at boiler setpoint parameter Δ°C -6.0 2014-03-06 10:32:05 (GMT-5) 3.0 2014-01-24 10:01:56 (GMT-5) 4.0 2013-12-27 10:28:22 (GMT-5)
843 Store charge is 0 % at the following temperature °C 40.0 2014-03-06 10:32:05 (GMT-5) 58.0 2014-01-24 10:00:57 (GMT-5) 30.0 2013-12-27 10:28:22 (GMT-5)
844 Start of store charging from charge % 86 2014-03-06 10:33:09 (GMT-5) 87 2014-03-06 10:32:05 (GMT-5) 75 2013-12-27 10:28:22 (GMT-5)
845 Start point 2 at store charge % 70 2014-03-06 10:33:09 (GMT-5) 65 2014-01-10 08:31:19 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
846 Start point 3 at store charge % 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
847 Start priority of the master boiler 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
848 Start priority of slave boiler 1 1 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
849 Start priority of slave boiler 2 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
850 Start priority of slave boiler 3 4 2013-12-27 10:28:14 (GMT-5) 4 2013-12-27 10:28:22 (GMT-5)
851 Display Temperatures in Fahrenheit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
852 Quick start if store discharge is greater than (% / 10min) 40 2014-03-06 10:33:09 (GMT-5) 20 2013-12-27 10:28:14 (GMT-5) 15 2013-12-27 10:28:22 (GMT-5)
853 Reduce the overall output of the cascade before the store is fully loaded % 0 2014-01-24 10:00:57 (GMT-5) 60 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
854 Opening of secondary air flap during troubleshooting/(preparation) % 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
855 Opening of air flap during pre-heating % 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
856 Opening of air flap during shutdown % 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
857 Control Pressure During Preparation (seal control) P 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
858 ID Fan Control During Preparation (seal control) % 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
859 Control Pressure Tolerance During Preparation (seal control) P 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
860 Under-pressure during pre-heating P 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
861 Pumpenausgang für das Tankentlastungs Ventil 129 2013-12-27 10:28:14 (GMT-5) 129 2013-12-27 10:28:22 (GMT-5)
862 Top store temp. when the start-up relief valve switches to bottom store °C 65.0 2013-12-27 10:28:14 (GMT-5) 65.0 2013-12-27 10:28:22 (GMT-5)
863 Outfeed setpoint for all days in program 7 °C 35.0 2013-12-27 10:28:14 (GMT-5) 35.0 2013-12-27 10:28:22 (GMT-5)
864 COM 2 is used as a MODBUS interface 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
865 MODBUS address 1 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
866 MODBUS protocol (1 - RTU / 2 - ASCII) 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
868 Under-pressure during shutdown P 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
869 Time feed screw is on until stoker screw % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
870 Broadband probe type (1 .. Bosch / 2 .. NTK) (3 .. LSM11 input) 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
871 Broadband probe calibration 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
872 Stoker monitoring active 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
873 Lambda (Broadband?) probe correction value -45 2013-12-27 10:28:14 (GMT-5) -45 2013-12-27 10:28:22 (GMT-5)
874 Minimum collector temperature °C 20.0 2013-12-27 10:28:14 (GMT-5) 20.0 2013-12-27 10:28:22 (GMT-5)
875 Solar charging to which store 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
876 Solar charging to which DHW tank 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
877 Boiler flue gas difference for fire out Δ°C 10.0 2013-12-27 10:28:14 (GMT-5) 10.0 2013-12-27 10:28:22 (GMT-5)
878 Control store requests according to system environment 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
879 According to system environment; store request shutdown delay of min 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
880 100 % boiler output from a store charge of % 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
881 0 % boiler output if store charge is over % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
882 Minimum loading rate T4 % 25.0 2013-12-27 10:28:14 (GMT-5) 25.0 2013-12-27 10:28:22 (GMT-5)
883 WOS runs every m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
884 Ash screw interval m 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
885 Boiler selection 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
886 Boiler selection 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
887 Boiler selection 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
888 Condenser cleaning interval (Heating hours) h 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
889 Condenser cleaning duration s 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
890 Condenser cleaning possible from 360 2013-12-27 10:28:14 (GMT-5) 360 2013-12-27 10:28:22 (GMT-5)
891 Condenser cleaning possible till 1320 2013-12-27 10:28:14 (GMT-5) 1320 2013-12-27 10:28:22 (GMT-5)
892 Correction value for external sensor Δ°C - 2013-12-27 10:28:14 (GMT-5) - 2013-12-27 10:28:22 (GMT-5)
893 Heating circuit module to which the external sensor is connected (0 = Core module) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
894 Boiler 1 Pumpe wird über HKP0 gesteuert 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
895 Combustion chamber temperature for Heating °C 500.0 2013-12-27 10:28:14 (GMT-5) 500.0 2013-12-27 10:28:22 (GMT-5)
896 Pulse per liter of flow through meter 2.0 2013-12-27 10:28:14 (GMT-5) 2.0 2013-12-27 10:28:22 (GMT-5)
897 Is an external flow through counter used 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
898 17 2013-12-27 10:28:14 (GMT-5) 17 2013-12-27 10:28:22 (GMT-5)
899 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
900 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
901 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
902 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
903 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
904 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
905 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
906 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
907 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
908 Electrical room air flap present 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
909 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
910 95 2013-12-27 10:28:14 (GMT-5) 95 2013-12-27 10:28:22 (GMT-5)
911 600 2013-12-27 10:28:14 (GMT-5) 600 2013-12-27 10:28:22 (GMT-5)
912 Refill cyclone after buffer charging? 1 2014-01-24 09:45:40 (GMT-5) 0 2013-12-27 10:28:14 (GMT-5) 1 2014-01-24 09:53:54 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
913 Opening of Air Flap during Ignition % 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
914 Start value of the O2 regulator % 35 2013-12-27 10:28:14 (GMT-5) 35 2013-12-27 10:28:22 (GMT-5)
915 Boiler Selection 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
916 Use room sensor input for room thermostat 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
917 Send a line break when ASCII data output on COM2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
918 Position 1 of change-over unit is used? 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
919 Position 2 of change-over unit is used? 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
920 Position 3 of change-over unit is used? 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
921 Clean after how many hours heating h 10.0 2014-01-24 09:48:55 (GMT-5) 8.0 2013-12-27 10:28:14 (GMT-5) 10.0 2014-01-24 09:51:12 (GMT-5) 8.0 2013-12-27 10:28:22 (GMT-5)
922 Vacuum + screw filling run-on applies after reaching the MAX fill level s 4 2013-12-27 10:28:14 (GMT-5) 0 2014-01-10 08:48:11 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
923 High temperature requirement because of DHW tank loading 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
924 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
925 Min. current monitoring with feed screw 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
926 For high temperature requirement DHW tank 01 don´t look at DHW tank 01 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
927 On-time of spray valve. Overall cycles 20 sec % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
928 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
929 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
930 Touchscreen with address 1 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
931 Touchscreen with address 2 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
932 Touchscreen with address 3 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
933 Touchscreen with address 4 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
934 Touchscreen with address 5 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
935 Touchscreen with address 6 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
936 Touchscreen with address 7 is allocated to the following heating circuit 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
937 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
938 Touchscreen with address 1 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
939 Touchscreen with address 2 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
940 Touchscreen with address 3 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
941 Touchscreen with address 4 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
942 Touchscreen with address 5 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
943 Touchscreen with address 6 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
944 Touchscreen with address 7 is allocated to the following DHW tank 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
945 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
946 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
947 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
948 41 2013-12-27 10:28:14 (GMT-5) 41 2013-12-27 10:28:22 (GMT-5)
949 Volume of the used storage tank L 2000 2013-12-27 10:28:14 (GMT-5) 2000 2013-12-27 10:28:22 (GMT-5)
950 Start delay of light barrier at sliding floor s 5.0 2013-12-27 10:28:14 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
951 Release delay of light barrier at sliding floor s 5.0 2013-12-27 10:28:14 (GMT-5) 5.0 2013-12-27 10:28:22 (GMT-5)
952 Cycles of sliding floor after s 600 2013-12-27 10:28:14 (GMT-5) 600 2013-12-27 10:28:22 (GMT-5)
953 Duration of cycles of sliding floor after s 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
954 maximum numbers of cycle for sliding floor 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
955 Is a hygienic layered tank used? 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
956 PWM setting for storage tank 1 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
957 PWM setting for storage tank 2 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
958 PWM setting for storage tank 3 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
959 PWM setting for storage tank 4 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
960 PWM setting for DHW tank 1 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
961 PWM setting for DHW tank 2 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
962 PWM setting for DHW tank 3 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
963 PWM setting for DHW tank 4 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
964 PWM setting for DHW tank 5 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
965 PWM setting for DHW tank 6 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
966 PWM setting for DHW tank 7 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
967 PWM setting for DHW tank 8 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
968 PWM setting for shunt pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
969 PWM setting for network pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
970 PWM setting for diff. control pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
971 PWM setting for boiler 2 pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
972 PWM setting for solar collector pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
973 Abort heating up --> ID fan off; close air flaps 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
974 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
975 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
976 Priority of suction position 2 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
977 Priority of suction position 3 1 2013-12-27 10:28:14 (GMT-5) 1 2013-12-27 10:28:22 (GMT-5)
978 Start of locking window for suction position with priority 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
979 End of locking window for suction position with priority 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
980 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
981 Black underpressure sensor cartridge installed (Type: 401.93000) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
982 Refill calculation active (Sensors have to be assigned correctly ) 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
983 Boiler standard variables have been adopted 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
984 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
985 2 2013-12-27 10:28:14 (GMT-5) 2 2013-12-27 10:28:22 (GMT-5)
986 5 2013-12-27 10:28:14 (GMT-5) 5 2013-12-27 10:28:22 (GMT-5)
987 80 2013-12-27 10:28:14 (GMT-5) 80 2013-12-27 10:28:22 (GMT-5)
988 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
989 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
990 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
991 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
992 50 2013-12-27 10:28:14 (GMT-5) 50 2013-12-27 10:28:22 (GMT-5)
993 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
994 8 2013-12-27 10:28:14 (GMT-5) 8 2013-12-27 10:28:22 (GMT-5)
995 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
996 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
997 40 2013-12-27 10:28:14 (GMT-5) 40 2013-12-27 10:28:22 (GMT-5)
998 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
999 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1000 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1001 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1002 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1003 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1004 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1005 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1006 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1007 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1008 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1009 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1010 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1011 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1012 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1013 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1014 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1015 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1016 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1017 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
1018 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1019 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1020 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1021 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1022 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1023 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1024 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1025 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1026 20 2013-12-27 10:28:14 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
1027 70 2013-12-27 10:28:14 (GMT-5) 70 2013-12-27 10:28:22 (GMT-5)
1028 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1029 130 2013-12-27 10:28:14 (GMT-5) 130 2013-12-27 10:28:22 (GMT-5)
1030 Maximum storage tank 1 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1031 Maximum storage tank 2 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1032 Maximum storage tank 3 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1033 Maximum storage tank 4 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1034 Maximum DHW tank 1 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1035 Maximum DHW tank 2 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1036 Maximum DHW tank 3 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1037 Maximum DHW tank 4 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1038 Maximum DHW tank 5 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1039 Maximum DHW tank 6 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1040 Maximum DHW tank 7 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1041 Maximum DHW tank 8 pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1042 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1043 Maximum speed for network pump % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1044 Maximum diff. Control pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1045 Maximum boiler 2 pump % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1046 Maximum circulation pump speed % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1047 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
1048 30 2013-12-27 10:28:14 (GMT-5) 30 2013-12-27 10:28:22 (GMT-5)
1049 150 2013-12-27 10:28:14 (GMT-5) 150 2013-12-27 10:28:22 (GMT-5)
1050 PWM setting for feeder pump 1 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1051 PWM setting for feeder pump 2 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1052 PWM setting for feeder pump 3 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1053 PWM setting for feeder pump 4 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1054 Invert output buffer for the relief valve 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1055 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1056 PWM setting for circulation pump 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1057 Maximum speed for feeder pump 1 % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1058 Maximum speed for feeder pump 2 % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1059 Maximum speed for feeder pump 3 % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1060 Maximum speed for feeder pump 4 % 100 2013-12-27 10:28:14 (GMT-5) 100 2013-12-27 10:28:22 (GMT-5)
1061 Minimum boiler 2 pump % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
1062 Minimum circulation pump speed % 45 2013-12-27 10:28:14 (GMT-5) 45 2013-12-27 10:28:22 (GMT-5)
1063 O2 controller limitation if this is not released % 35 2013-12-27 10:28:14 (GMT-5) 35 2014-01-10 08:48:11 (GMT-5) 20 2013-12-27 10:28:22 (GMT-5)
1064 Nominal current for feed screw A 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
1065 Nominal current for feed screw A 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
1066 In case of overcurrent, break for s 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
1067 During troubleshooting of feed screw, it turns backwards for s 1.0 2013-12-27 10:28:14 (GMT-5) 1.0 2013-12-27 10:28:22 (GMT-5)
1068 During troubleshooting of feed screw, it turns forwards for s 1.5 2013-12-27 10:28:14 (GMT-5) 1.5 2013-12-27 10:28:22 (GMT-5)
1069 10 2013-12-27 10:28:14 (GMT-5) 10 2013-12-27 10:28:22 (GMT-5)
1070 3 2013-12-27 10:28:14 (GMT-5) 3 2013-12-27 10:28:22 (GMT-5)
1071 Switch-on delay feed screw light barrier s 3.0 2013-12-27 10:28:14 (GMT-5) 3.0 2013-12-27 10:28:22 (GMT-5)
1072 Switch-off delay feed screw light barrier s 3.0 2013-12-27 10:28:14 (GMT-5) 3.0 2013-12-27 10:28:22 (GMT-5)
1073 High temp req due to boiler 1 charge 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1074 Temp 1 °C 80.0 2013-12-27 10:28:14 (GMT-5) 80.0 2013-12-27 10:28:22 (GMT-5)
1075 Temp 2 °C 130.0 2013-12-27 10:28:14 (GMT-5) 130.0 2013-12-27 10:28:22 (GMT-5)
1076 FGR Characteristics 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1077 WOS Monitoring Active 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1078 Screw 1 active 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1079 Screw 2 active 0 2013-12-27 10:28:14 (GMT-5) 0 2013-12-27 10:28:22 (GMT-5)
1080 Maximum idle time of screw m 60 2013-12-27 10:28:14 (GMT-5) 60 2013-12-27 10:28:22 (GMT-5)
1081 Switch-on delay feed screw light barrier s 3.0 2013-12-27 10:28:14 (GMT-5) 3.0 2013-12-27 10:28:22 (GMT-5)
1082 Switch-off delay feed screw light barrier s 3.0 2013-12-27 10:28:14 (GMT-5) 3.0 2013-12-27 10:28:22 (GMT-5)
1083 Maximum DHW tank flow temp Hc 1 °C 75.0 2015-02-17 15:45:11 (GMT-5) 75.0 2015-02-17 15:45:18 (GMT-5)
1084 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1085 Maximum DHW tank flow temp Hc 2 °C 75.0 2015-02-17 15:45:11 (GMT-5) 75.0 2015-02-17 15:45:18 (GMT-5)
1087 Control heating circuit according to program (NO -> heating circuit is switched off) HC 11 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1088 Control heating circuit according to program (NO -> heating circuit is switched off) HC 12 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1089 Control heating circuit according to program (NO -> heating circuit is switched off) HC 13 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1090 Control heating circuit according to program (NO -> heating circuit is switched off) HC 14 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1091 Control heating circuit according to program (NO -> heating circuit is switched off) HC 15 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1092 Control heating circuit according to program (NO -> heating circuit is switched off) HC 16 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1093 Control heating circuit according to program (NO -> heating circuit is switched off) HC 17 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1094 Control heating circuit according to program (NO -> heating circuit is switched off) HC 18 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1095 Solar - PWM setting for buffer tank - heat exchanger pump 0 2015-09-01 15:18:45 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1096 Solar - PWM setting for DHW tank - heat exchanger pump 0 2015-02-17 15:45:11 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1097 Password for boiler display -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1098 Password for Touch display with address 1 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1099 Password for Touch display with address 2 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1100 Password for Touch display with address 3 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1101 Password for Touch display with address 4 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1102 Password for Touch display with address 5 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1103 Password for Touch display with address 6 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1104 Password for Touch display with address 7 -1 2015-02-17 15:45:11 (GMT-5) -1 2015-02-17 15:45:18 (GMT-5)
1105 Deviation of room sensor from Touch display with address 1 Δ°C - 2015-02-17 15:45:11 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1106 Deviation of room sensor from Touch display with address 2 Δ°C - 2015-02-17 15:45:11 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1107 Deviation of room sensor from Touch display with address 3 Δ°C - 2015-09-01 15:18:46 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1108 Deviation of room sensor from Touch display with address 4 Δ°C - 2015-09-01 15:18:46 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1109 Deviation of room sensor from Touch display with address 5 Δ°C - 2015-02-17 15:45:11 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1110 Deviation of room sensor from Touch display with address 6 Δ°C - 2015-02-17 15:45:11 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1111 Deviation of room sensor from Touch display with address 7 Δ°C - 2015-02-17 15:45:11 (GMT-5) - 2015-02-17 15:45:18 (GMT-5)
1112 0 2015-02-17 15:45:11 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1113 Functon of Touch display with address 1 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1114 Functon of Touch display with address 2 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1115 Functon of Touch display with address 3 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1116 Functon of Touch display with address 4 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1117 Functon of Touch display with address 5 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1118 Functon of Touch display with address 6 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1119 Functon of Touch display with address 7 2 2015-02-17 15:45:11 (GMT-5) 2 2015-02-17 15:45:18 (GMT-5)
1120 153 2015-02-17 15:45:11 (GMT-5) 153 2015-02-17 15:45:18 (GMT-5)
1121 Countdown Startpoint 2035 2015-02-17 15:45:11 (GMT-5) 2035 2015-02-17 15:45:18 (GMT-5)
1123 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1124 Demoreler/Messesoftware StandardWerte uebernehmen/ Clear pending error 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1125 1 2016-04-04 13:33:47 (GMT-5) 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1126 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1127 Diff. control - Sensor monitoring 1 2015-02-17 15:45:11 (GMT-5) 1 2015-02-17 15:45:18 (GMT-5)
1128 Reset counter since last maintenance 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)
1130 0 2015-09-01 15:18:46 (GMT-5) 0 2015-02-17 15:45:18 (GMT-5)